C.1. Variables

device: General unit information

Note

these data will be redundant with some ups.* information during a transition period. The ups.* data will then be removed.

Name Description Example value

device.model

Device model

BladeUPS

device.mfr

Device manufacturer

Eaton

device.serial

Device serial number (opaque string)

WS9643050926

device.type

Device type (ups, pdu, scd)

ups

ups: General unit information

Name Description Example value

ups.status

UPS status

OL

ups.alarm

UPS alarms

OVERHEAT

ups.time

Internal UPS clock time (opaque string)

12:34

ups.date

Internal UPS clock date (opaque string)

01-02-03

ups.model

UPS model

SMART-UPS 700

ups.mfr

UPS manufacturer

APC

ups.mfr.date

UPS manufacturing date (opaque string)

10/17/96

ups.serial

UPS serial number (opaque string)

WS9643050926

ups.vendorid

Vendor ID for USB devices

0463

ups.productid

Product ID for USB devices

0001

ups.firmware

UPS firmware (opaque string)

50.9.D

ups.firmware.aux

Auxiliary device firmware

4Kx

ups.temperature

UPS temperature (degrees C)

042.7

ups.load

Load on UPS (percent)

023.4

ups.load.high

Load when UPS switches to overload condition ("OVER") (percent)

100

ups.id

UPS system identifier (opaque string)

Sierra

ups.delay.start

Interval to wait before restarting the load (seconds)

0

ups.delay.reboot

Interval to wait before rebooting the UPS (seconds)

60

ups.delay.shutdown

Interval to wait after shutdown with delay command (seconds)

20

ups.timer.start

Time before the load will be started (seconds)

30

ups.timer.reboot

Time before the load will be rebooted (seconds)

10

ups.timer.shutdown

Time before the load will be shutdown (seconds)

20

ups.test.interval

Interval between self tests (seconds)

1209600 (two weeks)

ups.test.result

Results of last self test (opaque string)

Bad battery pack

ups.display.language

Language to use on front panel (* opaque)

E

ups.contacts

UPS external contact sensors (* opaque)

F0

ups.efficiency

Efficiency of the UPS (ratio of the output current on the input current) (percent)

95

ups.power

Current value of apparent power (Volt-Amps)

500

ups.power.nominal

Nominal value of apparent power (Volt-Amps)

500

ups.realpower

Current value of real power (Watts)

300

ups.realpower.nominal

Nominal value of real power (Watts)

300

ups.beeper.status

UPS beeper status (enabled, disabled or muted)

enabled

ups.type

UPS type (* opaque)

offline

ups.watchdog.status

UPS watchdog status (enabled or disabled)

disabled

ups.start.auto

UPS starts when mains is (re)applied

yes

ups.start.battery

Allow to start UPS from battery

yes

ups.start.reboot

UPS coldstarts from battery (enabled or disabled)

yes

input: Incoming line/power information

Name Description Example value

input.voltage

Input voltage

121.5

input.voltage.maximum

Maximum incoming voltage seen

130

input.voltage.minimum

Minimum incoming voltage seen

100

input.voltage.nominal

Nominal input voltage

120

input.voltage.extended

Extended input voltage range

no

input.transfer.reason

Reason for last transfer to battery (* opaque)

T

input.transfer.low

Low voltage transfer point

91

input.transfer.high

High voltage transfer point

132

input.transfer.low.min

smallest settable low voltage transfer point

85

input.transfer.low.max

greatest settable low voltage transfer point

95

input.transfer.high.min

smallest settable high voltage transfer point

131

input.transfer.high.max

greatest settable high voltage transfer point

136

input.sensitivity

Input power sensitivity

H (high)

input.quality

Input power quality (* opaque)

FF

input.current

Input current (A)

4.25

input.current.nominal

Nominal input current (A)

5.0

input.frequency

Input line frequency (Hz)

60.00

input.frequency.nominal

Nominal input line frequency (Hz)

60

input.frequency.low

Input line frequency low (Hz)

47

input.frequency.high

Input line frequency high (Hz)

63

input.frequency.extended

Extended input frequency range

no

input.transfer.boost.low

Low voltage boosting transfer point

190

input.transfer.boost.high

High voltage boosting transfer point

210

input.transfer.trim.low

Low voltage trimming transfer point

230

input.transfer.trim.high

High voltage trimming transfer point

240

output: Outgoing power/inverter information

Name Description Example value

output.voltage

Output voltage (V)

120.9

output.voltage.nominal

Nominal output voltage (V)

120

output.frequency

Output frequency (Hz)

59.9

output.frequency.nominal

Nominal output frequency (Hz)

60

output.current

Output current (A)

4.25

output.current.nominal

Nominal output current (A)

5.0

Three-phase additions

The additions for three-phase measurements would produce a very long table due to all the combinations that are possible, so these additions are broken down to their base components.

Phase Count Determination

input.phases (3 for three-phase, absent or 1 for 1phase) output.phases (as for input.phases)

DOMAINs

Any input or output is considered a valid DOMAIN.

input (should really be called input.mains, but keep this for compat) input.bypass input.servicebypass

output (should really be called output.load, but keep this for compat) output.bypass output.inverter output.servicebypass

Specification (SPEC)

Voltage, current, frequency, etc are considered to be a specification of the measurement.

With this notation, the old 1phase naming scheme becomes DOMAIN.SPEC Example: input.current

CONTEXT

When in three-phase mode, we need some way to specify the target for most measurements in more detail. We call this the CONTEXT.

With this notation, the naming scheme becomes DOMAIN.CONTEXT.SPEC when in three-phase mode. Example: input.L1.current

Valid CONTEXTs
L1-L2  \
L2-L3   \
L3-L1    for voltage measurements
L1-N    /
L2-N   /
L3-N  /
L1  \
L2  for currrent and power measurements
L3  /
N  - for current measurement
Valid SPECs

Valid with/without context (ie. per phase or aggregated/averaged)

Name Description

current

Current (A)

current.maximum

Maximum seen current (A)

current.minimum

Minimum seen current (A)

peakcurrent

Peak current

voltage

Voltage (V)

voltage.nominal

Nominal voltage (V)

voltage.maximum

Maximum seen voltage (V)

voltage.minimum

Minimum seen voltage (V)

power

Apparent power (VA)

power.maximum

Maximum seen apparent power (VA)

power.minimum

Maximum seen apparent power (VA)

power.percent

Percentage of apparent power related to maximum load

power.maximum.percent

Max seen percentage of apparent power

power.minimum.percent

Min seen percentage of apparent power

realpower

Real power (W)

powerfactor

Power Factor (dimensionless value between 0.00 and 1.00)

crestfactor

Crest Factor (dimensionless value greater or equal to 1)

Valid without context (ie. aggregation of all phases):

Name Description

frequency

Frequency (Hz)

frequency.nominal

Nominal frequency (Hz)

EXAMPLES

Partial Three phase - Three phase example:

input.phases: 3
input.frequency: 50.0
input.L1.current: 133.0
input.bypass.L1-L2.voltage: 398.3
output.phases: 3
output.L1.power: 35700
output.powerfactor: 0.82

Partial Three phase - One phase example:

input.phases: 3
input.L2.current: 48.2
input.N.current: 3.4
input.L3-L1.voltage: 405.4
input.frequency: 50.1
output.phases: 1
output.current: 244.2
output.voltage: 120
output.frequency.nominal: 60.0

battery: Any battery details

Name Description Example value

battery.charge

Battery charge (percent)

100.0

battery.charge.low

Remaining battery level when UPS switches to LB (percent)

20

battery.charge.restart

Minimum battery level for UPS restart after power-off

20

battery.charge.warning

Battery level when UPS switches to "Warning" state (percent)

50

battery.voltage

Battery voltage (V)

24.84

battery.capacity

Battery capacity (Ah)

7.2

battery.current

Battery current (A)

1.19

battery.temperature

Battery temperature (degrees C)

050.7

battery.voltage.nominal

Nominal battery voltage (V)

024

battery.runtime

Battery runtime (seconds) Remaining battery runtime

1080

battery.runtime.low

when UPS switches to LB (seconds)

180

battery.alarm.threshold

Battery alarm threshold

0 (immediate)

battery.date

Battery change date (opaque string)

11/14/00

battery.mfr.date

Battery manufacturing date (opaque string)

2005/04/02

battery.packs

Number of battery packs

001

battery.packs.bad

Number of bad battery packs

000

battery.type

Battery chemistry (opaque (opaque string)

PbAc

battery.protection

Prevent deep discharge of battery

yes

battery.energysave

Switch off when running on battery and no/low load

no

ambient: Conditions from external probe equipment

Name Description Example value

ambient.temperature

Ambient temperature (degrees C)

25.40

ambient.temperature.alarm

Temperature alarm (enabled/disabled)

enabled

ambient.temperature.high

Temperature threshold high (degrees C)

40

ambient.temperature.low

Temperature threshold low (degrees C)

5

ambient.temperature.maximum

Maximum temperature seen (degrees C)

37.6

ambient.temperature.minimum

Minimum temperature seen (degrees C)

18.1

ambient.humidity

Ambient relative humidity (percent)

038.8

ambient.humidity.alarm

Relative humidity alarm (enabled/disabled)

enabled

ambient.humidity.high

Relative humidity threshold high (percent)

80

ambient.humidity.low

Relative humidity threshold high (percent)

10

ambient.humidity.maximum

Maximum relative humidity seen (percent)

60

ambient.humidity.minimum

Minimum relative humidity seen (percent)

13

outlet: Smart outlet management

Note

n stands for the outlet index. For more information, refer to the NUT outlets management and PDU notes chapter of the user manual. A special case is "outlet.0" which is equivalent to "outlet", and represent the whole set of outlets of the device.

Name Description Example value

outlet.n.id

Outlet system identifier (opaque string)

1

outlet.n.desc

Outlet description (opaque string)

Main outlet

outlet.n.switch

Outlet switch control (on/off)

on

outlet.n.status

Outlet switch status (on/off)

on

outlet.n.switchable

Outlet switch ability (yes/no)

yes

outlet.n.autoswitch.charge.low

Remaining battery level to power off this outlet (percent)

80

outlet.n.delay.shutdown

Interval to wait before shutting down this outlet (seconds)

180

outlet.n.delay.start

Interval to wait before restarting this outlet (seconds)

120

outlet.n.current

Current (A)

0.19

outlet.n.current.maximum

Maximum seen current (A)

0.56

outlet.n.realpower

Current value of real power (W)

28

outlet.n.voltage

Voltage (V)

247.0

outlet.n.powerfactor

Power Factor (dimensionless value between 0 and 1)

0.85

outlet.n.crestfactor

Crest Factor (dimensionless, equal to or greater than 1)

1.41

outlet.n.power

Apparent power (VA)

46

driver: Internal driver information

Name Description Example value

driver.name

Driver name

usbhid-ups

driver.version

Driver version (NUT release)

X.Y.Z

driver.version.internal

Internal driver version (if tracked separately)

1.23.45

driver.parameter.xxx

Parameter xxx (ups.conf or cmdline -x) setting

(varies)

driver.flag.xxx

Flag xxx (ups.conf or cmdline -x) status

enabled (or absent)

server: Internal server information

Name Description Example value

server.info

Server information

Network UPS Tools upsd vX.Y.Z - http://www.networkupstools.org/

server.version

Server version

X.Y.Z